Assistance to Firefighter Grant Program (AFGP)
Minimum Equipment on Water
Tender
NFPA 1901 Chapter 7 Mobile Water Supply Fire Apparatus
Pump - If the apparatus is equipped with
a fire pump, the pump shall meet the requirements of NFPA 1901
Chapter 16.
The mobile water supply apparatus shall
be equipped with a water tank(s) that meets the requirements of NFPA
1901 Chapter 19 and that has a minimum certified capacity (combined, if
applicable) of 1000 gallon.
A minimum of 20 cubic feet of enclosed
weather-resistant compartmentation meeting the requirements of NFPA
1901 Section 15.1 shall be provided for the storage of equipment.
A minimum hose storage area of 6 cubic
feet for 2.5 in. or larger fire hose that meets the requirements of
NFPA 1901 Section 15.10 shall be provided.
If the apparatus is equipped with a fire
pump, two areas, each a minimum of 3.5 cubic feet, to accommodate 1.5
in. or larger preconnected fire hose lines shall be provided.
If the mobile water supply fire
apparatus is equipped with a pump, the requirements in NFPA 1901 7.6.1
through 7.6.3 shall apply.
A minimum of 15 ft of soft suction hose
or 20 ft of hard suction hose shall be carried.
Where hard suction hose is provided, a
suction strainer shall be furnished.
Where hard suction hose is provided, the
friction and entrance loss of
the combination suction hose and strainer shall not exceed the losses
listed in NFPA 1901 Table 16.2.4.1(b) or Table 16.2.4.1(c).
Where soft suction hose is provided, it
shall have couplings compatible
with the local hydrant outlet connection on one end and the pump intake
connection on the other end.
Suction hose shall meet the requirements
of NFPA 1961, Standard on Fire Hose.
The purchaser shall specify whether hard
or soft suction hose is to be
provided, the length and size of the hose, the type and size of the
couplings, the manner in which the suction hose is to be carried on the
apparatus, and the style of brackets desired.
The equipment listed in 7.7.2 and 7.7.3
shall be available on the mobile water supply fire apparatus before the
apparatus is placed in service.
Brackets or compartments shall be
furnished so as to organize and mount the specified equipment.
A detailed list of who is to furnish the
items and the method for
organizing and mounting these items shall be supplied by the purchasing
authority.
The mobile water supply apparatus shall
be equipped with at least 200 ft of 2.5 in. or larger fire hose.
If the mobile water supply apparatus is
equipped with a fire pump, the following shall be provided:
- 400
ft of 1.5 in., 1.75 in., or 2 in. fire hose
- Two
combination spray nozzles, 95 gpm
minimum
Mobile water supply fire apparatus shall
be equipped with at least the following equipment:
- One 6 lb
flathead or pickhead axe mounted in a bracket fastened to the
apparatus
- One 6 ft
or longer pike pole or plaster hook mounted in a bracket fastened to
the apparatus
- Two
portable hand lights mounted in brackets fastened to the apparatus
- One
approved dry chemical
portable fire extinguisher with a minimum 80-B:C rating mounted in a
bracket fastened to the apparatus
- One 2.5
gal or larger water extinguisher mounted in a bracket fastened to the
apparatus
- One SCBA
complying with NFPA 1981, Standard on Open-Circuit Self-Contained
Breathing Apparatus for Fire and Emergency Services,
for each assigned seating position, but not fewer than two, mounted in
brackets fastened to the apparatus or stored in containers supplied by
the SCBA manufacturer
- One spare
SCBA cylinder for
each SCBA carried, each mounted in a bracket fastened to the apparatus
or stored in a specially designed storage space(s)
- One first
aid kit
- Two
combination spanner wrenches mounted in a bracket fastened to the
apparatus
- One
hydrant wrench mounted in a bracket fastened to the apparatus
- One double
female adapter, sized to fit 2.5 in. or larger fire hose, mounted in a
bracket fastened to the apparatus
- One double
male adapter, sized to fit 2.5 in. or larger fire hose, mounted in a
bracket fastened to the apparatus
- Two
wheel chocks, mounted in
readily accessible locations, each designed to hold the apparatus, when
loaded to its maximum in-service weight, on a 10 percent grade with the
transmission in neutral and the parking brake
released
If the mobile water supply apparatus is
equipped with a fire pump, and none of the pump intakes required by
NFPA 1901 section16.6.1
are valved, a hose appliance that is equipped with one or more gated
intakes with female swivel connection(s) compatible with the supply
hose used on one side and a swivel connection with pump intake threads
on the other side shall be carried. Any intake connection 3.5 in. or
larger shall include a pressure relief device that meets the
requirements of 16.6.6.
If the mobile water supply apparatus is
equipped with a fire pump, a
rubber mallet for use on suction hose connections shall be carried in a
bracket fastened to the apparatus.